аrt.60
For automatic testing of switching points in density monitors
This device allows precise, quick and easy verification of the switching points. The density monitor to be tested is mounted onto the device by means of a quick clamping device or a plug-in coupling (depending on the connection). After starting the measurement the pressure is automatically increased to filling pressure, the switching points are activated and recorded. The switching points can be stored in the system with serial number and temperature indication allowing a data file to be produced for documentation.
Advantages & functions
Technical data
Weight 17 kg
Interface USB and Ethernet
Operating temperature 0 to +45 °C
Frequency 50 - 60 Hz
Accuracy Accuracy of the pressure sensor (0 - 50 °C): ≤ 0.1 % FS
Dimensions (W x H x D) 538 x 269 x 406 mm
Operating voltage 100 - 240 V
Mains fuse 2 x 3.15 A (T)